Uninterruptible Power
Supply
80 kVA
and
120 kVA
Installation and Operation
Manual
164201396 Rev. A
9
335
Vue de la page 0
1 2 3 4 5 6 ... 99 100

Résumé du contenu

Page 1

Uninterruptible Power Supply 80 kVA and 120 kVA Installation and Operation Manual 164201396 Rev. A 9335

Page 2

ix Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103 Basic System Configurations These basic UPS sys

Page 3

This page left intentionally blank W-2 Powerware 9335 (80 kVA – 120 kVA) Installation and Operation 164201396 REV A. 07110

Page 4 - Table of Contents

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation x 164201396 REV. A 071103 Section II – Operation • Chapter 5 – Understanding UPS

Page 5 - Section II Operation

xi Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103 Safety Considerations The UPS cabinet is designe

Page 6

Section I Installation

Page 7

This page left intentionally blank

Page 8

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 1-1 164201396 REV A 071103 1.1 Installing the UPS The complete UPS cabinet is s

Page 9

1-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 1.1.2 Preparing Your Site For your UPS to ope

Page 10 - 164201396 REV. A 071103

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 1-3 164201396 REV A 071103 1.1.5 Inspecting and Unpacking Each Cabinet The first tas

Page 11 - 164201396 REV. A 071103

1-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 1. Carefully inspect the outer packaging fo

Page 12 - Getting Help

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 2-1 164201396 REV A 071103 2.1 Preliminary Installation Information Refer

Page 14

2-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 2.2 UPS Cabinet Installation To install an

Page 15 - Getting Started

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 2-3 164201396 REV A 071103 2.2.2 Installing External Battery Power Wiring The Power

Page 16 - 1.1.2 Preparing Your Site

2-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 4. If the installation is for a sin

Page 17 - 164201396 REV A 071103

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 2-5 164201396 REV A 071103 2. Remove Customer Interface conduit landing plate from

Page 18

2-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 completed Installation Checklist to be sure yo

Page 19

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 3-1 164201396 REV A 071103 3.1 Important Safety Instructions The Powerware 9335 UPS

Page 20 - Cabinet from the Pallet

3-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation

Page 21

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 4-1 164201396 REV A 071103 4.1 Installation Procedures Figure 4–1.

Page 22

4-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 Table 4 – 1. Remote EPO

Page 23 - 2.4 Initial Startup

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 164201396 REV. A 071103 Section II Operation

Page 24 - Installation Checklist

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation ii 164201396 REV. A 071103 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE IN

Page 25

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 This page left intentionally blank

Page 26

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-1 164201396 REV. A 071103 5.1 Looking Inside the UPS System The Powerware 9335 is

Page 27 - EMERGENCY OFF

5-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 BatteryChargerRectifierEMI FilterEMI FilterInput Fi l te

Page 28 - WIRES (2)

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-3 164201396 REV. A 071103 5.2 Normal, Battery and Bypass Modes The UPS system func

Page 29 - Operation

5-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 5.2.1 Normal Mode Figure 5–2 shows the path of electric

Page 30 - 164201396 REV A 071103

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-5 164201396 REV. A 071103 The DC boost converter derives power from the unregulated D

Page 31 - Understanding UPS Operation

5-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 5.2.2 Bypass Mode The UPS automatically switches

Page 32

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-7 164201396 REV. A 071103 contactor and together are wired to enable the inverter and

Page 33 - 164201396 REV. A 071103

5-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 5.2.3 Battery Mode The UPS transfers to battery mo

Page 34 - 5.2.1 Normal Mode

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-9 164201396 REV. A 071103 While in battery mode, the UPS will enunciate an audible ho

Page 35

iii Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103 A Introduction . . . . . . . . . . . .

Page 36 - 5.2.2 Bypass Mode

5-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 5.2.4 Maintenance Bypass Mode An internal maintenan

Page 37

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 5-11 164201396 REV. A 071103 5.3 Functional Description The UPS is an online double-

Page 38 - 5.2.3 Battery Mode

5-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 or constant voltage mode (temperature compensated, avai

Page 39

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 6-1 164201396 REV. A 071103 6.1 General The UPS system should function automatically

Page 40 - Maintenance Bypass Mode

6-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 6.2 UPS Operational Controls The UPS has many standar

Page 41

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 6-3 164201396 REV. A 071103 6.2.3 Maintenance Bypass Switch An internal Maintenance

Page 42 - 5.3.6 Maintenance Bypass

6-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 6.4 Options and Accessories Contact your sales represe

Page 43 - 6.1 General

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 6-5 164201396 REV. A 071103 6.5 Safety Considerations The UPS enclosure is designed f

Page 44 - 6.2.1 Control Panel

6-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 6.6 Symbols, Controls, and Indicators These symbols m

Page 45 - 6.3 UPS Standard Features

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-1 164201396 REV. A 071103 7.1 Description This chapter describes the UPS Control

Page 46 - 6.4 Options and Accessories

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation iv 164201396 REV. A 071103 Section II Operation 5 Understanding UPS Operation

Page 47 - 6.5 Safety Considerations

7-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 7.2 Using the Control Panel The Control Panel provide

Page 48

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-3 164201396 REV. A 071103 INDICATOR INDICATOR STATUS MEANING ALARM OFF RED + BUZZE

Page 49 - the Control Panel

7-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 If, for security or emergency reasons, it is neces

Page 50 - 7.2 Using the Control Panel

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-5 164201396 REV. A 071103 7.3.2 LCD Display Structure and Navigation The menu str

Page 51 - 7.2.3 Pushbutton Functions

7-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 7.3.3 Main Menu Screen DESCRIPTION LCD DISPLAY

Page 52 - 7.3.1 Status Screens

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-7 164201396 REV. A 071103 • Battery Voltage • Battery Charger Current • Disc

Page 53 - PERFORM

7-8 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 7.3.7 UPS Data DESCRIPTION LCD DISPLAY • Infor

Page 54 - SET-UP SERVICE

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-9 164201396 REV. A 071103 7.3.9 Set-Up Service DESCRIPTION LCD DISPLAY • Th

Page 55 - 7.3.6 Commands Screen

7-10 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 7.4 O perating Modes 7.4.1 “ON LINE” Mode (INVERTER MO

Page 56 - 7.3.8 Set-Up User

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 7-11 164201396 REV. A 071103 inverter within 5 milliseconds. When utility power retur

Page 57 - 7.3.9 Set-Up Service

v Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103 7.3.7 UPS Data . . . . . . . . . . . . . . . .

Page 58 - 7.4 O perating Modes

7-12 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 7.4.4 Parallel Isolator (IA2) The UPS unit is provide

Page 59

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 8-1 164201396 REV. A 071103 8.1 Operation The following procedures provide instr

Page 60

8-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 LED Indicator Color LINE 1 Green LINE 2 Green BYPAS

Page 61 - Instructions

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 8-3 164201396 REV. A 071103 12. Rotate the Maintenance Bypass Switch IA1 to the “O” (O

Page 62

8-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 2. If the loads are all disconnected, press simultane

Page 63

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 8-5 164201396 REV. A 071103 • Rotate the Maintenance Bypass Switch IA1 to “I” (ON

Page 64

8-6 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 This page left intentionally b

Page 65

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 9-1 164201396 REV. A 071103 9.1 Alarms In the event of an alarm condition, the red

Page 66

9-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 9.3 Fault Identification and Correction The major ala

Page 67 - 9.1 Alarms

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 10-1 164201396 REV. A 071103 10.1 X – Slot Communication Modules This section descr

Page 68

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation vi 164201396 REV. A 071103 Figure 1 – 1 Powerware 9335 (80 kVA and 120 kVA) UPS

Page 69 - Communications

10-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 Figure 10–1. X–S

Page 70 - Control Panel

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 10-3 164201396 REV. A 071103 power environment. If a power emergency occurs, the soft

Page 71

10-4 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 This page left intentionally blan

Page 72

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 11-1 164201396 REV. A 071103 11.1 Generator ON Facility The generator ON facility

Page 73 - 11.1 Generator ON Facility

11-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 This page left intentionally bl

Page 74

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 12-1 164201396 REV. A 071103 12.1 General The components inside the UPS cabinet ar

Page 75 - 12.1 General

12-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 12.3 Performing Preventive Maintenance The UPS system

Page 76

Powerware 9335 (80 kVA and120 kVA) Installation and Operation 13-1 164201396 REV. A 071103 13.1 System Information The UPS systems are housed in

Page 77

13-2 Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV A 071103 13.3 UPS System Output DC Ripple less than 1% volt

Page 78 - 13.3 UPS System Output

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-1 164201396 REV A 07/11/2003 A The information in this appendix will help yo

Page 79 - 164201396 REV A 07/11/2003

vii Powerware 9335 (80 kVA and 120 kVA) Installation and Operation 164201396 REV. A 071103 Table 4 – 1 Remote EPO Wire Terminations

Page 80 - Powerware 9335 – 80 kVA

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9335 – 80 kVA Ratings Units Rating 50/60 HzkVA W 80 Basic unit ra

Page 81 - Powerware 9335 – 120 kVA

Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for Powerware 9335 – 120 kVA Ratings Units Rating 50/60 HzkVA kW 120 96 Basic

Page 82

7. Terminals are UL rated at 90o C. Refer to Table C for power cable terminations and Table D for conduit requirements. Figure A–1 shows the loca

Page 83

11. External overcurrent protection is not provided by this product, but is required by codes. Refer to A and B for wiring requirements. If an outp

Page 84

Table G. Customer Interface Inputs and Outputs Terminal Name Description X1 Emergency Power Off X1 – 1 and X1 – 2 (no polarity) X2 Generator On

Page 85

Table H. Definition of pin connections on JD2 (25 pin DB-25P/F) Pin Contact Signal Function 1 Mains failure 2 ALARM MNS Mains present 3

Page 86

Table I. Definition of pins on JD1 and interface cable connections to 9 or 25 pin connectors. 5 . . .9 3 2 15 9 . .

Page 87 - During Full Load Operation

Table J. Equipment Weight Weight Kg (lbs.) Powerware Model Shipping Installed Point Loading 9335 – 80 kVA 360 (792) 333 (733) 4 at 83 (183)

Page 88

External Battery Powerware 9335 80 kVA and 120 kVA Front View showing customer connections

Page 89

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation A-11 164201396 REV A 07/11/2003 Fi

Page 90

Powerware 9335 (80 kVA and 120 kVA) Installation and Operation viii 164201396 REV. A 071103 Powerware 9335 UPS true double conversion online

Page 91

STANDARD VERSION (DUAL INPUT FEED CONNECTION) SHOWN 0 kVA) Installation and Operation 164201396 REV A 07/11/2003 Figure A–4. Power Terminal

Page 92

HGFEDCBAChecked by :Rep l ace :Date:Date:S igna tu re :S igna tu re :S igna tu re :ModificationModificationS06-0001ULADate:Sheet : 1 of : 5HGFEDCBA1

Page 93

1 2345678910HGFEDCBAChecked by :Replace :Date:Date:Signature :Signature :Signature :ModificationModificationS06-0001ULADate:Sheet :5 of : 5HGFEDCBA1

Page 94

700 mm. (27.6 inches) 1800 mm. (70.9 inches)Removable Conduit Landing Plate Figure A–7. UPS Cabinet Dimensions (Rear View) Powerware 9335 (80 kV

Page 95

750 mm. (29.6 inches) 700 mm. (27.6 inches)1800 mm. (70.9 Figure A–8. UPS Cabinet Dimensions

Page 100 - 164201396 REV A. 071103

LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE PRODUCTS Subject to the conditions herein, Invensys Powerware (Powerware ®) warrants solely, to th